But what if you prefer to run ESX on ESX instead of Workstation?
Full article at:http://www.vcritical.com/2009/05/vmware-esx-4-can-even-virtualize-itself/
I believe the Next Generation Computing is Software Defined Infrastructure on top of the robust physical infrastructure. You can ask me anything about enterprise infrastructure (virtualization, compute, storage, network) and we can discuss it deeply on this blog. Don't hesitate to contact me.
But what if you prefer to run ESX on ESX instead of Workstation?
Full article at:A BTU is a British thermal unit, which is the measure of energy to raise one CC of water one degree Celsius.
But you probably want to know about airflow in CFM (not water), and the amount of cooling (or heating) available in 1 cfm or airflow.
In Houston, we tend to cool things more than heat. We also try to drive moisture out of the air (dehumidify), but I won't discuss that now. The general equation to answer your question is like this: Qsens = cfm * 1.08 * (Tin - Tout) <-- "delta T"
You need to determine what your "delta T" is. For cooling a space to 75degF (23.89 degC), your dT is usually 20degF (-6.67 degC) with your supply air temperature (SA=55degF 12.78degC) and your return air temperature (RA=75degF 23.89 degC). This has been idealized and simplified. For cooling, 1cfm will do about 21.6btu/h of cooling. For heating, (SA=90/32.2, RA=68, 1cfm => 23.76btu/h)